Ablerex ODIN Plus RT Online Rack Tower UPS
Ablerex ODIN Plus RT Online Rack Tower UPS Ablerex ODIN Plus RT brings online double-conversion power protection to NAS storage, servers and network equipment in a short-depth rack or tower arrangement. DSP control and a pure sine-wave output provide a considered foundation for equipment that needs a stable supply through everyday mains disturbances. The front display makes load, battery status and operating conditions easier to assess before an interruption becomes a rushed decision. Match the UPS to the equipment’s real power demand and the time needed for a controlled shutdown, with the communication interface and rack support planned as part of the installation. Highlights Continuous Power Conditioning Online double-conversion topology and DSP control Pure sine-wave output with a 0.9 output power factor Wide input-voltage operating range, subject to load Practical Deployment Rack or tower arrangement in a short-depth chassis LCD status and estimated runtime information Standard battery system with optional management and runtime expansion Key Features Protect the Working System Power interruptions can stop file services, disconnect switches and interrupt a server while work is still being written. The UPS provides a controlled power path and battery-backed time for supported equipment. Pair it with a tested shutdown plan so the available battery energy has a clear purpose. Read the Status Before an Outage The display reports electrical conditions, connected load and battery information, with audible or visible alarms for important events. Runtime is an estimate rather than a fixed entitlement; periodic checks help confirm that the installed load still leaves sufficient time for shutdown. Plan the Rack Around the Hardware The short-depth chassis can suit installations where front-to-back space is constrained. Check the rack’s usable depth, support method and weight rating, allowing room for cables and ventilation. A tower arrangement is another option when a rack is not appropriate. Connect Shutdown and Monitoring Properly RS-232 and supported optional management interfaces allow the UPS to participate in a suitable monitoring or shutdown arrangement. Exact operating-system support, NAS compatibility and optional card choice need to be checked for the intended setup. Network shutdown does not become available simply by connecting the UPS to mains power. Treat Battery Care as Part of Continuity Battery-backed time changes as batteries age and as equipment is added. Keep the UPS ventilated, follow the maintenance instructions and test the shutdown procedure. A UPS supports a power-loss response; separate, current backups remain necessary for deletion, ransomware and storage failure. Summary Choose Ablerex ODIN Plus RT when online power conditioning, a short-depth installation and clear local status are important to the deployment. Build the solution around the measured load, required shutdown time and verified management connection, with the physical support and battery-care arrangements confirmed before installation. Frequently Asked Questions What Does an Online UPS Protect Against?ExpandCollapse In normal online operation, the UPS converts incoming AC to DC and regenerates the AC output. This helps supported equipment ride through mains disturbances and provides battery-backed time during an outage. It does not replace a separate backup of the files stored on a NAS or server. How Do I Choose the Right UPS Size?ExpandCollapse Check both the total watts and VA of the connected equipment, including startup demand, and leave headroom. Then select a battery runtime that allows the equipment to shut down safely. A UPS power rating is not a promise of a particular number of minutes. Are Batteries Included in This Configuration?ExpandCollapse The listed short-depth ODIN Plus RT configuration uses its standard internal sealed lead-acid battery system. An extended battery bank, optional management card and installation accessories are separate unless specifically included in your order. Can It Shut Down a NAS or Server Safely?ExpandCollapse A controlled shutdown needs a supported communication connection, compatible software and correct settings on the NAS or server. Check the exact NAS model and UPS interface before purchase. An SNMP/Web card is optional, and compatibility must be confirmed rather than assumed. Will It Fit My Rack?ExpandCollapse The listed chassis occupies 4U and is 432mm deep before cables and service clearance. Check the usable rack depth, load rating, ventilation and supporting shelf or rail arrangement. Rack ears alone should not be treated as confirmation of adequate support. How Long Will the Backup Last?ExpandCollapse Runtime changes with the actual connected load, battery condition and temperature. Share the equipment list, measured watts and required shutdown time so the battery arrangement can be checked. Keep current independent data backups even when a UPS is installed.
可在 3005, Ubi Avenue 3, #01-88 提货
通常在 2 至 4 个工作日内备妥(公共假期除外)
Ablerex ODIN Plus RT Online Rack Tower UPS
描述
Ablerex ODIN Plus RT Online Rack Tower UPS
Ablerex ODIN Plus RT brings online double-conversion power protection to NAS storage, servers and network equipment in a short-depth rack or tower arrangement. DSP control and a pure sine-wave output provide a considered foundation for equipment that needs a stable supply through everyday mains disturbances.
The front display makes load, battery status and operating conditions easier to assess before an interruption becomes a rushed decision. Match the UPS to the equipment’s real power demand and the time needed for a controlled shutdown, with the communication interface and rack support planned as part of the installation.
Highlights
Continuous Power Conditioning
- Online double-conversion topology and DSP control
- Pure sine-wave output with a 0.9 output power factor
- Wide input-voltage operating range, subject to load
Practical Deployment
- Rack or tower arrangement in a short-depth chassis
- LCD status and estimated runtime information
- Standard battery system with optional management and runtime expansion
Key Features
Protect the Working System
Power interruptions can stop file services, disconnect switches and interrupt a server while work is still being written. The UPS provides a controlled power path and battery-backed time for supported equipment. Pair it with a tested shutdown plan so the available battery energy has a clear purpose.
Read the Status Before an Outage
The display reports electrical conditions, connected load and battery information, with audible or visible alarms for important events. Runtime is an estimate rather than a fixed entitlement; periodic checks help confirm that the installed load still leaves sufficient time for shutdown.
Plan the Rack Around the Hardware
The short-depth chassis can suit installations where front-to-back space is constrained. Check the rack’s usable depth, support method and weight rating, allowing room for cables and ventilation. A tower arrangement is another option when a rack is not appropriate.
Connect Shutdown and Monitoring Properly
RS-232 and supported optional management interfaces allow the UPS to participate in a suitable monitoring or shutdown arrangement. Exact operating-system support, NAS compatibility and optional card choice need to be checked for the intended setup. Network shutdown does not become available simply by connecting the UPS to mains power.
Treat Battery Care as Part of Continuity
Battery-backed time changes as batteries age and as equipment is added. Keep the UPS ventilated, follow the maintenance instructions and test the shutdown procedure. A UPS supports a power-loss response; separate, current backups remain necessary for deletion, ransomware and storage failure.
Summary
Choose Ablerex ODIN Plus RT when online power conditioning, a short-depth installation and clear local status are important to the deployment. Build the solution around the measured load, required shutdown time and verified management connection, with the physical support and battery-care arrangements confirmed before installation.
Frequently Asked Questions
What Does an Online UPS Protect Against?
In normal online operation, the UPS converts incoming AC to DC and regenerates the AC output. This helps supported equipment ride through mains disturbances and provides battery-backed time during an outage. It does not replace a separate backup of the files stored on a NAS or server.
How Do I Choose the Right UPS Size?
Check both the total watts and VA of the connected equipment, including startup demand, and leave headroom. Then select a battery runtime that allows the equipment to shut down safely. A UPS power rating is not a promise of a particular number of minutes.
Are Batteries Included in This Configuration?
The listed short-depth ODIN Plus RT configuration uses its standard internal sealed lead-acid battery system. An extended battery bank, optional management card and installation accessories are separate unless specifically included in your order.
Can It Shut Down a NAS or Server Safely?
A controlled shutdown needs a supported communication connection, compatible software and correct settings on the NAS or server. Check the exact NAS model and UPS interface before purchase. An SNMP/Web card is optional, and compatibility must be confirmed rather than assumed.
Will It Fit My Rack?
The listed chassis occupies 4U and is 432mm deep before cables and service clearance. Check the usable rack depth, load rating, ventilation and supporting shelf or rail arrangement. Rack ears alone should not be treated as confirmation of adequate support.
How Long Will the Backup Last?
Runtime changes with the actual connected load, battery condition and temperature. Share the equipment list, measured watts and required shutdown time so the battery arrangement can be checked. Keep current independent data backups even when a UPS is installed.
规格
Ablerex ODIN Plus RT Online Rack Tower UPS
Specifications describe the standard 230V-region short-depth configuration. Optional management hardware, extended battery banks and installation accessories are separate unless stated.
| UPS Design | |
|---|---|
| Topology | Online double conversion with DSP control |
| Installation | Rack or tower convertible; short-depth chassis |
| Rated Output | 3000VA / 2700W |
| Output Power Factor | 0.9 |
| Input | |
| Phase and Wiring | Single phase with protective earth |
| Voltage Range | 110–300V AC; allowable range depends on load |
| Frequency | 40–70Hz auto sensing |
| Input Power Factor | Greater than 0.99 at 100% linear load |
| Output | |
| Waveform | Pure sine wave |
| Selectable Voltage | 200 / 208 / 220 / 230 / 240V AC, subject to supplied regional configuration |
| Frequency | 50 / 60Hz; selectable ±1Hz or ±3Hz synchronisation range |
| Crest Factor | 3:1 |
| Connections | 230V brochure configuration: 6 × IEC C13 and 1 × IEC C19; confirm supplied rear panel and cable requirements |
| Battery and Runtime | |
| Battery Type | Sealed lead-acid, maintenance-free |
| Standard Battery System | 6 × 12V batteries; 72V DC for the listed short 3000VA chassis |
| Recharge Time | Approximately 4 hours to 90% under manufacturer test conditions |
| Cold Start | Supported |
| Runtime | Load and battery dependent; size the system for the required shutdown time rather than the VA rating alone |
| Monitoring and Protection | |
| Display | Voltage, frequency, load, battery level, output current and estimated runtime |
| Operating Modes | Normal online, ECO and constant-voltage/constant-frequency modes |
| Standard Interfaces | RS-232, EPO and RJ11/RJ45 protection interfaces in the 230V brochure configuration |
| Optional Management | USB, dry-contact relay and SNMP/Web interfaces; exact card compatibility must be confirmed separately |
| Alarms | Mains failure, low battery, bypass transfer and system fault |
| Protection | Overload, excessive temperature, short circuit, discharge and overcharge protection |
| Physical | |
| Rack Height | 4U |
| Dimensions W × H × D | 440 × 176 × 432mm |
| Net Weight | 25kg for the standard short 3000VA chassis |
| Installation Planning | Allow rack support, ventilation, earthing and access for battery maintenance; rack support hardware is not assumed included |
| Environment | |
| Operating Temperature | 0–40°C |
| Operating Humidity | 0–90% RH, non-condensing |
| Operating Altitude | Up to 1500m without derating |
| Acoustic Noise | Up to 50dBA at 1m in front, per manufacturer conditions |